LPCB Approved Intelligent smoke detector Addressable fire alarm system
works with TC series addressable fire alarm system LPCB TC-5109 alarm panel fire fighting
Infrared scattering principle
Non-polarized two-wire
Drift compensation and fault detecting function
Reporting dirt fault
Hotel, restaurant, warehouse, library, office building, teaching
building, power plant and other places
Approvals:LPCB(EN54-7) CE

Technical Specifications
Operating voltage Loop 24V(18.5V~26V)
Operating current Standby current: ≤0.3mA;Alarm current: ≤0.8mA
Operating Environment Temperature: -10°C~+55°C,Relative Humidity: ≤95%, non-condensing
Indicator Red,Flashes when polling,Illuminates in alarm
Ingress protection rating IP23
Material and color of enclosure ABS; Milky white
Coding method Electronically coding
Code range 1~255
Weight About 110g
Mounting hole distance 60mm
Dimension 100mm×51mm (with base)